The commonest reason an installation slips is not the machine. It is the supply. Electrical work needs lead time and sometimes a utility application, so this is worth settling the week you place the order rather than the week before delivery.
What the machine draws
A laser cutter's total load is the source, the chiller, the drives, the extraction and the control cabinet together — not the laser's rated wattage. As a guide, a 1000W–3000W machine wants roughly 15 kW at 32 A, and a 4000W–6000W machine roughly 30 kW at 60 A. Our team confirms the exact figure for your configuration during the pre-installation survey.
What the supply has to be
- Three phase, 380–415 V, 50 Hz
- A dedicated line to the machine, not shared with welding sets or compressors
- A proper earth — this one is not optional, and poor earthing causes faults that look like control problems
- Cable sized for the run length, not just the current
Voltage stability matters more than headroom
Laser sources and servo drives are sensitive to voltage swing. In areas with an unstable supply a servo stabiliser is worth fitting from day one, and if your supply drops out regularly a UPS on the control system prevents a mid-sheet stop becoming a scrapped sheet and a re-home.
The rest of the site checklist
- Compressed air, clean and dry, if the configuration uses it
- Assist gas cylinders or a generator, with a safe route for the lines
- Extraction ducted outside, with the run planned before the machine is positioned
- A level floor with enough clearance to load sheet and open the cabinet
- Crane or forklift access to the bed at loading height
We survey the site before dispatch and give you the electrical and services requirement in writing, so the contractor can work to it while the machine is still in transit.